amana air conditioner codes

If you’re looking for help fixing your Amana air conditioner, look no further! Our comprehensive Amana air conditioner repair guide will explain common issues, provide troubleshooting tips, and show you how to read your model’s error codes.

CODE: FP.
PROBLEM: Freeze Protection Engaged. The room temperature measured by the wireless remote thermostat or indoor ambient thermistor active sensor falls below 40°F.
FIX: No Action required. This setting will disengage when the room temperature rises above 43°F.

CODE: Fd.
PROBLEM: Front Desk switch is closed. All outputs are switched off.
FIX: Open front desk switch to allow occupant unit operation.

CODE: Eo.
PROBLEM: Un-Configured Service Board – All operation held awaiting configuration.
FIX: Enter Configuration Menu and set “C3” to “C” for coolers with electric heat or “H” for heat pumps.

CODE: EH.
PROBLEM: Emergency Hydronic Engaged. The EHH switch is closed. Compressor is switched off.
FIX: Open front emergency hydronic switch to allow occupant unit operation.

CODE: LS.
PROBLEM: Load Shedding Engaged. The LS switch is closed. Compressor and Electric heat is switched off.
FIX: Open load shedding switch to allow occupant unit operation.

CODE: On.
PROBLEM: Control is configured to respond to a wired thermostat.
FIX: No action if a wired thermostat is being used.Otherwise, see Configuration Settings.

CODE: oP.
PROBLEM: Open Door Lockout (DS1 & DS2 open; wireless).
FIX: Close Room Door. Unit will not condition space with door open.

CODE: nP.
PROBLEM: Window Switch Lockout – (LS & INN open).
FIX: Close Room Door or Window. Unit will not condition space with door or window open.

CODE: HP.
PROBLEM: Heat Sentinel – (WIAT > u3).
FIX: No action required. This setting will disengage when the room temperature falls.

CODE: Ur.
PROBLEM: Un-Rented Status (EHH & INN or wireless).
FIX: Front Desk needs to set to Rented mode (if applicable).

CODE: F1.
PROBLEM: Indoor Ambient Thermistor reads outside the range -20°F to 200°F & the wireless thermostat is not communicating to the unit control or Indoor Ambient Thermistor (IAT) without a wireless remote thermostat reads outside the range -20°F to 200°F.
FIX: Replace black Indoor Ambient Thermistor or Wireless Remote Thermostat.

CODE: F2.
PROBLEM: Wireless Remote Thermostat failure.
FIX: Replace Wireless Thermostat.

CODE: F3.
PROBLEM: Indoor Ambient Thermistor reads outside the range -20°F to 200°F.
FIX: Replace black Indoor Ambient Thermistor.

CODE: F4.
PROBLEM: Indoor Coil Thermistor either above or below operating tolerances.
FIX: Replace Red Indoor Coil Thermistor.

CODE: F5.
PROBLEM: Wireless Thermostat failure.
FIX: Attempt to rebind Wireless Thermostat or Replace Wireless Thermostat.

CODE: F6.
PROBLEM: Indoor Discharge Thermistor either above or below operating tolerances.
FIX: Replace Yellow Indoor Discharge Thermistor.

CODE: Fb.
PROBLEM: Low Remote Battery Warning.
FIX: Replace Batteries in Wireless Devices.

CODE: H1.
PROBLEM: High Voltage Protection engaged. Power supply voltage is to high.
FIX: Check for incoming power at correct voltage.

CODE: br.
PROBLEM: Brown Out Protection engaged. Power was lost or voltage is low.
FIX: Check for incoming power at correct voltage.

CODE: L6.
PROBLEM: Discharge Air Too Hot.
FIX: Clean Filter or Remove Air Blockage.

CODE: LC.
PROBLEM: Outdoor Coil Thermistor temperature high.
FIX: Clean Condenser Coils, Check Fan for fault. Code will reset after cleaning.

CODE: C2.
PROBLEM: Indoor Air Recirculation. Large delta between thermostat and return.
FIX: Clean Filter or Remove Air Blockage or Close Vent Door or Improve indoor to outdoor seal.

CODE: C5.
PROBLEM: Outdoor Coil temperature too high for outdoor ambient temperature.
FIX: Check for Blocked Outdoor Air or Clean Coil.

CODE: C1.
PROBLEM: Indoor Coil is freezing up.
FIX: Clean filter, Check for fan and blower operation, Check for Refrigerant loss or Restricted capillary tube.

CODE: C3.
PROBLEM: Indoor Coil is freezing up.
FIX: Clean filter, Check for fan and blower operation, Check for Refrigerant loss or Restricted capillary tube.

CODE: C4.
PROBLEM: Indoor Coil froze up.
FIX: Clean filter, Check for fan and blower operation, Check for Refrigerant loss or Restricted capillary tube.

CODE: C6.
PROBLEM: Poor Unit Performance.
FIX: Check for blower motor, compressor, or electric heat operation.

CODE: C7.
PROBLEM: Indoor Freezing Lockout (ICT – IAT > 20) +10 Min.
FIX: Clean filter, Check for fan and blower operation, Check for Refrigerant loss or Restricted capillary tube.

amana air conditioner codes

 


What Our Clients Are Saying About Us

I would like to recommend your company to anyone

Wing Sang LeungNorth York, Ontario

Work was done neatly. Can barely see the pipe that was installed

Ellen McaleerOshawa, Ontario

KDM's cost was amazingly reasonable compared to all other quotes

Don GibsonMarkham, Ontario

I would recommend this company to anyone who is looking for a professional job at a reasonable price

Don BlakeWhitby, Ontario

I would recommend KDM Home Gas to anyone looking for quality home repair services

Giselle DharmiWhitby, Ontario

Thank you guys! We couldn’t be happier

Maria & Steve HalvorsonPickering, Ontario

I highly recommend KDM Home

Frank HowardWhitby, Ontario

I would recommend KDM Home & Gas to anyone looking for great service at a good price.

Josh TaylorAjax, Ontario

Great guys Daniel and Shane did an excellent job

George TrajkovskiAjax, Ontario

KDM did our fireplace gas line and heat venting

Maria & Steve Halvorson Oshawa, Ontario