If you’re looking for help fixing your McQuay furnace, look no further! Our comprehensive McQuay furnace repair guide will explain common issues, provide troubleshooting tips, and show you how to read your model’s error codes.

CODE: SLOW GREEN FLASH
PROBLEM: Normal operation

CODE: SLOW AMBER FLASH
PROBLEM: Normal operation with call for heat

CODE: RAPID RED FLASH
PROBLEM: Twinning error, incorrect 24V phasing.
FIX: Check twinning wiring. Flame sense current is below 1.5 microamps

CODE: RAPID AMBER FLASH
PROBLEM: Check and clean flame sensor. Check for proper gas flow. Verify that current is greater than 1.5 microamps at flame current test pad.

CODE: 4 AMBER FLASHES
PROBLEM: The control is receiving a “Y” signal from the thermostat without a “G” signal, indicating improper thermostat wiring.

CODE: 1 RED FLASH
PROBLEM: This indicates that flame was sensed when there was not a call for heat.
FIX: The control will turn on both the inducer motor and supply air blower. A gas valve that leaks or is slow closing would typically cause this fault.

CODE: 2 RED FLASHES
PROBLEM: This indicates that the normally open pressure switch contacts are stuck in the closed position.
FIX: The control confirms these contacts are open at the beginning of each heat cycle. This would indicate a faulty pressure switch or miswiring. This indicates the normally open pressure switch contact did not close after the inducer was energized.

CODE: 3 RED FLASHES
PROBLEM: This could be caused by a number of problems: faulty inducer, blocked vent pipe broken pressure switch hose or faulty pressure switch.

CODE: 4 RED FLASHES
PROBLEM: This indicates that the main limit switch has opened its normally closed contacts.
FIX: The control will operate the supply air blower and inducer. This condition may be caused by: dirty filter, improperly sized duct system, incorrect blower speed setting, incorrect firing rate or faulty blower motor. Also, this fault code could be caused by a blown fuse located on the control board.

CODE: 5 RED FLASHES
PROBLEM: This fault is indicated if the normally closed contacts in the rollout switch opens.
FIX: The rollout control is manually reset. If it has opened, check for proper combustion air, proper inducer operation, and primary heat exchanger failure or burner problem. Be sure to reset the switch and cycle power (24 VAC) to the control after correcting the failure condition. Also, this fault code could be caused by a blown fuse located on the control board.

CODE: 6 RED FLASHES
PROBLEM: This indicates that after the unit was operating, the pressure switch opened 4 times during the call for heat.
FIX: If the main blower is in a “Delay on” mode, it will complete it, and any subsequent delay off period. The furnace will lock out for one hour and then restart.

CODE: 7 RED FLASHES
PROBLEM: This fault code indicates that the flame could not be established. This no-light condition occurred 3 times (2 retries) during the call for heat before locking out.
FIX: Low gas pressure, faulty gas valve, dirty or faulty flame sensor, faulty hot surface ignitor or burner problem may cause this. The furnace will lock out for one hour and then restart.

CODE: 8 RED FLASHES
PROBLEM: This fault is indicated if the flame is lost 5 times (4 recycles) during the heating cycle.
FIX: This could be caused by low gas pressure, dirty or faulty flame sensor or faulty gas valve. The furnace will lock out for one hour and then restart.

CODE: 9 RED FLASHES
PROBLEM: Indicates reversed line voltage polarity or grounding problem.
FIX: Both heating and cooling operations will be affected. check polarity at furnace and branch. Check furnace grounding. Check that flame probe is not shorted to chassis.

CODE: 10 RED FLASHES
PROBLEM: Flame sensed with no call for heat.
FIX: Check gas valve and gas valve wiring This indicates that a primary or auxiliary limit switch has opened its normally-closed contacts and has remained open for more than five minutes.

CODE: 11 RED FLASHES
PROBLEM: This condition is usually caused by a failed blower motor or blower wheel.
FIX: Cycle power (24 VAC) to the control to reset the hard lockout condition after correcting the failure condition.

CODE: 12 RED FLASHES
PROBLEM: This code indicates an open igniter circuit.
FIX: This could be a disconnected or loose wire or a cracked or broken igniter.

CODE: STEADY ON RED
PROBLEM: Control failure.
FIX: Replace control board.

CODE: 60-MINUTE AUTOMATIC RESET FROM LOCKOUT
PROBLEM: This control includes a “watchdog” type circuit that will reset from a lockout condition after 60 minutes. Operational faults 6, 7, 8 will be reset. This provides protection to an unoccupied structure if a temporary condition exists causing a furnace malfunction. An example would be a low incoming gas supply pressure preventing unit operation When the gas pressure is restored, at some point the “watchdog” would restart the unit and provide heat for the house.

CODE: IGNITION CONTROL FLAME SENSE LEVELS
PROBLEM: Normal flame sense current is approximately 3.7 microamps DC Low flame signal warning starts at 1.5 microamps. Low flame signal control lockout point is 0.1 microamps DC.

mcquay furnace codes

 


What Our Clients Are Saying About Us

I would like to recommend your company to anyone

Wing Sang LeungNorth York, Ontario

Work was done neatly. Can barely see the pipe that was installed

Ellen McaleerOshawa, Ontario

KDM's cost was amazingly reasonable compared to all other quotes

Don GibsonMarkham, Ontario

I would recommend this company to anyone who is looking for a professional job at a reasonable price

Don BlakeWhitby, Ontario

I would recommend KDM Home Gas to anyone looking for quality home repair services

Giselle DharmiWhitby, Ontario

Thank you guys! We couldn’t be happier

Maria & Steve HalvorsonPickering, Ontario

I highly recommend KDM Home

Frank HowardWhitby, Ontario

I would recommend KDM Home & Gas to anyone looking for great service at a good price.

Josh TaylorAjax, Ontario

Great guys Daniel and Shane did an excellent job

George TrajkovskiAjax, Ontario

KDM did our fireplace gas line and heat venting

Maria & Steve Halvorson Oshawa, Ontario